GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 201

Advertising
background image

Introduction to FlexLogic

191

11

PHASE LOSS 2…30

Same set of operands as shown for PHASE
LOSS 1

ELEMENT:
PLC Inputs

PLC INPUT 1...256

PLC Input x register is equal to 1

ELEMENT:
Power Reversal

POWER REVERSAL 1 ALARM PKP
POWER REVERSAL 1 ALARM OP
POWER REVERSAL 1 ALARM DPO

POWER REVERSAL 1 TRIP PKP
POWER REVERSAL 1 TRIP OP

POWER REVERSAL 1 TRIP DPO

Reverse Power 1 alarm function in pickup
Reverse Power 1 alarm activated
Reverse Power 1 alarm function not in
pickup
Reverse Power 1 trip function in pickup
Reverse Power 1 relay function tripped
breaker
Reverse Power 1 trip function not in pickup

POWER REVERSAL 2…30

Same set of operands as shown for POWER
REVERSAL 1

ELEMENT:
Short Time
Overcurrent

SHORT TIME 1 PKP
SHORT TIME 1 OP
SHORT TIME 1 DPO

Short Time Overcurrent 1 in pickup
Short Time Overcurrent 1 tripped breaker
Short Time Overcurrent 1 not in pickup

SHORT TIME 2…30

Same set of operands as shown for SHORT
TIME 1

ELEMENT:
Synch Check

SYNC CHECK 1 DEAD S OP
SYNC CHECK 1 DEAD S DPO

SYNC CHECK 1 SYNC OP

SYNC CHECK 1 SYNC DPO

SYNC CHECK 1 CLS OP
SYNC CHECK 1 CLS DPO
SYNC CHECK 1 V1 ABOVE MIN

SYNC CHECK 1 V1 BELOW MAX

SYNC CHECK 1 V2 ABOVE MIN

SYNC CHECK 1 V2 BELOW MAX

Synch Check 1 dead source has operated
Synch Check 1 dead source has dropped
out
Synch Check 1 in synchronization has
operated
Synch Check 1 in synchronization has
dropped out
Synch Check 1 close has operated
Synch Check 1 close has dropped out
Synch Check 1 V1 is above the minimum
live voltage
Synch Check 1 V1 is below the maximum
dead voltage
Synch Check 1 V2 is above the minimum
live voltage
Synch Check 1 V2 is below the maximum
dead voltage

SYNC 2…12

Same set of operands as show above for
SYNC CHECK 1

Table 11-2 Entellisys FlexLogic operands

OPERAND TYPE

OPERAND SYNTAX

OPERAND DESCRIPTION