4 “or” board, Figure 10-3 layout of “or” board – GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 173

Advertising
background image

Discrete inputs/outputs

169

10

10.1.1.4 “OR” board

The “OR” board is used only in redundant configurations of discrete I/Os. In redundant
configurations, outputs on two or four discrete I/O boards (installed in two CPUs) control the
states of output relays. The “OR” board is used to electrically isolate outputs on boards. Only
outputs are connected to the “OR” board. The board logically “ORs” the signals from the outputs
of two CPUs, and the resulting signal controls output relays. There is no need to “OR” signals
from input relays. Each board can handle up to 16 outputs from each CPU. Screw terminals with
letter A designate discrete outputs from CPU A, and those with letter B designate discrete
outputs from CPU B. Connections from the outputs on terminal blocks are made in pairs. The
“OR” board takes the “OR” of each pair and outputs a single result for each pair. Depending on
the number of discrete outputs in the systems, more “OR” boards can be used.

Figure 10-3 Layout of “OR” board

1A

1B

2A

2B

3A

3B

4A

4B

5A

5B

6A

6B

7A

7B

8A

8B

9A

9B

10A

10B

11A

11B

12A

12B

13A

13B

14A

GND

OUT1

GND

OUT2

GND

OUT3

GND

OUT4

GND

OUT5

GND

OUT6

GND

OUT7

GND

OUT8

GND

OUT9

GND

OUT10

GND

OUT11

GND

OUT12

GND

OUT13

GND

GN

GN

GN

FROM TERMINAL BLOCKS

TO RELAY BLOCKS

+5V

Advertising