Alarms and events description and system troubleshooting guide

281

A

Dropout LT Overcurrent

Long time overcurrent function has dropped out of
pickup

Breaker Trip LT Overcurrent

Breaker tripped due to long time overcurrent
condition

Pickup Ground Fault

Ground fault function has entered pickup

Dropout Ground Fault

Ground fault function has dropped out of pickup

Breaker Trip Ground Fault

Breaker tripped due to ground fault condition

Alarm Ground Fault

Ground fault alarm has operated

Invalid Setting IOC Change
Rejected

Attempt to enable or disable IOC has been rejected The setting entered for IOC enable was

inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting IOC Pickup
Change Rejected

Attempt to change IOC pickup setting has been
rejected

The value entered for the IOC pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Invalid Setting GF Change
Rejected

Attempt to enable or disable ground fault has been
rejected

The setting entered for GF enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting GF Pickup
Change Rejected

Attempt to change the ground fault pickup setting
has been rejected

The value entered for the GF pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

Invalid Setting ST Change
Rejected

Attempt to enable or disable short time has been
rejected

The setting entered for ST enable was
inconsistent with the protection options
configured at the Compartment ID. Verify
that the protection options are correct.

Invalid Setting ST Pickup Change
Rejected

Attempt to change the short time pickup setting
has been rejected

The value entered for the ST pickup setting
was inconsistent with the protection options
and frame size configured at the
Compartment ID. Select a value that is
consistent with these parameters.

GF Trip Priority Disabled ZSI Not
Optioned

During initialization, GF Tripping Priority function
checks out whether ZSI is optioned in the system. If
it finds out that ZSI is not optioned, this event is
logged

Alarm Pickup Ground Fault

Logged when current is above pickup level of
ground fault alarm functionality.

Table A-9 Protection Relay Events

Event

Description

Notes and Troubleshooting tips