Discrete I/O

186

10

Figure 10-14 GOOSE Inputs

Controls
Update HMI button:
Before configuring GOOSE, you must download the current configuration
from the CPU.

GOOSE Input parameters:
Import CID button:
Import or select a IEC 61850 compliant CID file. This CID file must be
generated by the publisher device. It must contain the exact data definition of the GOOSE
message broadcasted by the publisher to be configured.

IED name, Access PT and Data Index are the fields in the publisher’s CID file and are used to
assign the data element in the GOOSE message to an Entellisys GOOSE Input.

The IED Name: The IED name or GO ID specified by the publisher’s CID file.

Access PT: Publisher’s CID file may contain a number of “Configurations” - only one of which
can be pushed out onto the network. This information should be contained within the CID file
itself.

Data Index: In the GOOSE message (as defined by the CID file) there is a specified number of
data items. These items could be any type. The Data Index is the index of the data item of
interest in the CID file.

Status: Once the reboot has finished, the active CPU will be listening for input messages. The
health status and Value will indicate both if the CPU is receiving data from the configured
publisher, what the value is and the error type if it is failing.

RX? indicator: Green when the Goose inputs are correctly configured. Red if there is a failure.

Value: When RX? Is green, this will indicate the value (0 or 1) of the goose input. If RX? is red, it
will contain the relevant error message.