IEC 61850 - GOOSE I/O

187

10

Table 10-2 GOOSE Input troubleshooting

Message

Explanation

Solution

Input Time to Live Expired

The GOOSE message is periodically refreshed by
the publisher. This message indicates that the
subscriber function in Entellisys is no longer
receiving GOOSE messaging from the subscriber.

Check network connectivity and GOOSE
configuration on the subscriber device.

Input Out of Sequence Detected

GOOSE message retransmission from publisher
is out of sequence.

Check network connectivity and GOOSE
configuration on the publisher device.

Input Configuration Revision
Mismatch

Configuration Revision mismatch between
publisher GOOSE message and its cid/icd file.

Check publisher cid/icd file “confRev” tag
and GOOSE configuration on the publisher
device.

Input Need Commissioning

Commission in GOOSE message is not set.

Check GOOSE configuration on the
publisher device.

Input Test Mode

Test Mode in GOOSE message is enabled.

Check GOOSE configuration on the
publisher device.

Input Goose Control Block
Reference Mismatch

Control Block Reference mismatch between
publisher GOOSE message and its cid/icd file.

Check publisher cid/icd file “GoCBRef” tag
and GOOSE configuration on the publisher
device.

Input App ID Mismatch

App ID mismatch between publisher GOOSE
message and its cid/icd file.

Check publisher cid/icd file “GoID” or
“AppID” tag and GOOSE configuration on
the publisher device.

GOOSE Control Block Initialization
Failure

Data Set mismatch between publisher GOOSE
message and its cid/icd file.

Check publisher cid/icd file “DatSet” tag and
GOOSE configuration on the publisher
device.

Input Incorrect Data Type

Entellisys subscriber only recognize discrete
inputs with Boolean type.

Configure GGIO Boolean output at
publisher.

Input Data Item Not Configured
Data Index Mapping Error
Input Data Set Mismatch

Publisher data item either not configured
correctly or missing.

Check HMI GOOSE I/O screen “DATA INDEX”
field and verify the data index is available at
publisher and its cid/icd file.

OSI File Configuration Failure

OSI file not resided at Entellisys CPU.

Close Entellisys HMI and reapply GOOSE
Input setting from HMI.

File Read Failure

Entellisys HMI fails to configure Entellisys
subscriber configuration files.

Check HMI GOOSE Input setting and reapply
GOOSE Input setting.