GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 294

Advertising
background image

Alarms and events

282

A

Alarm Dropout Ground Fault

Logged when current goes below dropout level of
ground fault alarm functionality.

GF Trip Priority Suspended

This event is no longer needed. We are simplifying
the implementation and removing dependencies
on ZSI type as well as ZSI enabled/disabled state.
As a result this event will be removed.

GF Trip Priority Resumed

This event is no longer needed. We are simplifying
the implementation and removing dependencies
on ZSI type as well as ZSI enabled/disabled state.
As a result this event will be removed.

GF Trip Priority Disabled MSGF
Optioned

Logged during initialization when GF Tripping
Priority function detects MSGF option in the system.
Function disables itself at this point

GF Trip Priority Operated

Logged when function modifies time delay of GF
protection element of any breaker that takes part in
GF tripping priority scheme.

High Current Transient Relay

HCTR Waveforms Max Count
Reached

Logged when maximum number of waveforms
have been triggered by the function

HCTR Waveforms Counter Reset Logged when user reset triggered waveform

counter

Alarm Pickup High Current
Trigger

Logged when current goes above pickup level.

Alarm Dropout High Current
Trigger

Logged when current goes below dropout level

Alarm High Current Trigger

Logged when function operated

Reduced Energy Let - Thru (RELT)

RELT Mode ON / OFF

Logged when a breaker goes into or out of RELT
mode

RELT Mode Multipoint ON / OFF

Logged when Multi-point goes into or out of RELT
mode

RELT Mode System Wide ON /
OFF

Logged when System Wide goes into or out of RELT
mode

RELT Mode - ON / OFF request
from Initiating Breaker

Logged when an associated breaker initiates RELT
mode on a breaker

See section

8.1.4

RELT Groups

on page 144

RELT Mode - ON / OFF request
from Modbus Device

Logged when a Modbus device initiates RELT mode
on a breaker

See section

8

Reduced Energy Let-Thru

Mode on page 139

Table A-9 Protection Relay Events

Event

Description

Notes and Troubleshooting tips

Advertising