Single-point functions

78

5

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage. If the option is enabled, the blocking voltage setting is 10% of the nominal
voltage.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.

Figure 5-7 Settings for Over Frequency Relay

5.2.3.5 Usage

Event logging
The following events are logged for the over frequency relay in the Entellisys HMI:

Alarm Pickup Over Frequency – Alarm only over frequency relay has entered pickup.

Alarm Over Frequency – Alarm only over frequency relay has operated.

Alarm Dropout Over Frequency – Alarm only over frequency relay has dropped out of pickup.

Voltage Below Overfreq Alarm Blocking Voltage – The voltage has dropped below the alarm
only over frequency blocking voltage threshold.

Voltage Above Overfreq Alarm Blocking Voltage – The voltage has exceeded the alarm only
over frequency blocking voltage threshold.

Pickup Over Frequency – Over frequency relay has entered pickup.

Breaker Trip Over Frequency – Over frequency relay has operated.

Dropout Over Frequency – Over frequency relay has dropped out of pickup.

Voltage Below Over Frequency Blocking Voltage – The voltage has dropped below the over
frequency blocking voltage threshold.