3 events, 4 configuration events, 5 confirmation events – GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 134

Advertising
background image

Multi-point functions

134

7

Figure 7-11 ZSI events

7.4.7.3 Events

Events logged by the ZSI can be grouped into three categories: configuration, confirmation, and
operation events. These events are described below.

7.4.7.4 Configuration events

This category has only one event.

Protection Suspended ZSI File Error. This event is logged when there is any problem with the
ZSI configuration file. This file is stored internally in CPUs by the HMI during the ZSI
configuration process.

7.4.7.5 Confirmation events

This category consists of eight events. “X” in the descriptions below stands for zone number and
it can assume values of 1 to 4.

ZSI Zone X Enabled. This event is logged when the ZSI zone is enabled from the HMI. There
can be a total of 4 variants of this event, one for each zone.

ZSI Zone X Disabled. This event is logged when the ZSI zone is disabled from the HMI. There
can be a total of 4 variants of this event, one for each zone.

Advertising