GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 203

Advertising
background image

Introduction to FlexLogic

193

11

Some operands can be renamed by the user. The operands that can be renamed are the names
of contact inputs/outputs and virtual inputs/outputs. If the user changes the default name of
any of these operands, the assigned name appears in the relay list of operands. The default
names are shown in the FlexLogic operands table (Table 11-2).

The operators available in FlexLogic are listed in Table 11-3.

INPUTS/OUTPUTS:
Virtual Outputs

Virtual Output 1 On

Virtual Output 480 On

Flag is set, logic = 1

Flag is set, logic = 1

Breaker Control commands available as
virtual outputs:
Open Flux Shifter
Open Shunt Trip
Trip Flux Shifter
Trip Shunt Trip
Close
Network Interlock Lockout
Network Interlock Lockout Reset

Table 11-3 FlexLogic operators

Type

Syntax

Descriptions

Notes

Editor

Copy

Copy a parameter from an equation list.

Paste

Paste a parameter in an equation list.

Insert

Insert a parameter in an equation list.

Delete

Delete a parameter from an equation list.

End

END

The first END encountered signifies the
last entry in the list of processed
FlexLogic parameters.

One Shot

POSITIVE ONE SHOT One shot that responds to a positive

going edge.

A 'one shot' refers to a
single input gate that
generates a pulse in
response to an edge on the
input. The output from a
'one shot' is True (positive)
for only one pass through
the FlexLogic equation.
There is a maximum of 64
'one shots'.

NEGATIVE ONE
SHOT

One shot that responds to a negative
going edge.

DUAL ONE SHOT

One shot that responds to both the
positive and negative going edges.

Table 11-2 Entellisys FlexLogic operands

OPERAND TYPE

OPERAND SYNTAX

OPERAND DESCRIPTION

Advertising