Reduced Energy Let-Thru Mode

150

8

NOTE: If a ZSI zone member is offline and another member enters RELT mode, the system will
select the safest time delay to prevent equipment damage.

8.3 Alarms and Events

When Reduced Energy Let-Thru Mode is enabled/disabled, an event is displayed in the HMI
Events Log as follows:

HMI Events

• RELT - ON Request For [breaker name] By [User name] - Logged when user requests to

turn ON single point RELT mode for a breaker

• RELT - OFF Request For [breaker name] By [User name] - Logged when user requests

to turn off single point RELT mode for a breaker

• RELT-Factory Request Reset For [breaker name];[user name] - Logged when factory

user requests to override a lock on a breaker

• RELT - Factory Request Reset [breaker name] - Logged when factory user requests to

override all locks for a breaker from Non-Master HMI

• RELT - Admin Request Reset For [breaker name];[user name] - Logged when

administrator user requests to override lock on a breaker

• RELT - Factory Request Reset For [breaker name]; Modbus Device - Logged when

factory user requests to override lock(s) (either one or all) for single point RELT mode
that was set by a Modbus device

• RELT - Admin Request Reset For [breaker name]; Modbus Device - Logged when

administrator user requests to override a lock for single point RELT mode that was set
by a Modbus device

• RELT - Factory Request Reset For [breaker name]; RELT Grp - Logged when factory

user requests to override lock(s) for single point RELT mode that was set by RELT Group

Single-point Events

• RELT Mode - ON Request From User
• RELT Mode - OFF Request From User
• RELT Mode - ON Request From FlexLogic
• RELT Mode - OFF Request From FlexLogic
• RELT Mode - ON Request From Initiating Breaker
• RELT Mode - OFF Request From Initiating Breaker
• RELT Mode - ON Request From Modbus Device
• RELT Mode - OFF Request From Modbus Device
• RELT Mode ON
• RELT Mode OFF

Multi-point Events

• RELT Mode Multipoint - ON Request From User