GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 192

Advertising
background image

Discrete I/O

188

10

File Parse Failure

Invalid “File name”/“IED name”/“AccessPoint
name” or Publisher cid/icd file format not
supported by Entellisys.

1.Check HMI GOOSE I/O screen “FILENAME”,
“IEDNAME”, “ACCESS PT” fields and reapply
GOOSE Input setting.
2.Verify publisher “APPID” is in range: 0 to
0xFFFF.
3.Verify publisher “orCat” <Val> is 1. May
need to modify publisher cid/icd file directly.
4.Verify “DataSet” is available and valid at
publisher and its cid/icd file. Entellisys only
supports GGIO data item (set) and Boolean
data type.

Data Type/Item Creation Failure

Data type/Item not supported by Entellisys.
Entellisys only supports GGIO data item and
Boolean data type.

Check GOOSE configuration on the
publisher device.

MAC Address Initialization Failure
Destination MAC Address
Mismatch

Invalid or incorrect publisher destination MAC
address.

Check GOOSE configuration on the
publisher device and use Entellisys HMI to
load new publisher cid/icd files to Entellisys
subscriber components.

VLAN Priority Parse Failure
VLAN ID Parse Failure

Publisher cid/icd file contains invalid VLAN
priority / VLAN ID.

Check GOOSE configuration on the
publisher device.

All other error code

Entellisys internal error.

Record error code and contact GE support.

Table 10-2 GOOSE Input troubleshooting

Message

Explanation

Solution

Advertising