Demand Metering Alarms

55

4

4.8.2 Setup

To set the settings for the Demand Alarm
1.
On the Main Menu, click User Settings, and then select Metering & Waveforms.
2. Click the Demand Alarm tab.
Settings

Figure 4-14 Demand Alarm settings page

Demand Alarm Selection: Select the alarm instance 1 through 16

Breaker Selection: Lists all installed breakers.

Over Demand / Under Demand Alarm Settings groups

Enabled: Enable the alarm
Pickup Setting: Set the pickup threshold from -5000 to 5000 KW (excluding 0) in 100 KW

increments.

Sub-Interval Length: Set the subinterval length from 1 to 900 in increments of 1.
Delay Setting (No of Subintervals): Configure the Interval length in terms of number of

demand sub-intervals from 1 to 15 in increments of 1. The product of subinterval and
interval setting cannot exceed 3600 seconds.