2 setup – GE Industrial Solutions Entellisys 5.0 User Manual User Manual
Page 55
Demand Metering Alarms
55
4
4.8.2 Setup
To set the settings for the Demand Alarm
1. On the Main Menu, click User Settings, and then select Metering & Waveforms.
2. Click the Demand Alarm tab.
Settings
Figure 4-14 Demand Alarm settings page
Demand Alarm Selection: Select the alarm instance 1 through 16
Breaker Selection: Lists all installed breakers.
Over Demand / Under Demand Alarm Settings groups
• Enabled: Enable the alarm
• Pickup Setting: Set the pickup threshold from -5000 to 5000 KW (excluding 0) in 100 KW
increments.
• Sub-Interval Length: Set the subinterval length from 1 to 900 in increments of 1.
• Delay Setting (No of Subintervals): Configure the Interval length in terms of number of
demand sub-intervals from 1 to 15 in increments of 1. The product of subinterval and
interval setting cannot exceed 3600 seconds.