GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 274

Advertising
background image

Alarms and events

262

A

Attention: Flash File Error in
[CPU A/B/Messngr]. Unable to
disable Flash Pgm
Mode.Replace CPU

Contact GE Service for CPU replacement

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution: Firmware Dwnld
Failed. Err Reading Messnger
Status for [Breaker(s)]

An error was detected in confirming the status of a
Messenger prior to upgrading its firmware.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution: Firmware Dwnld
Failed. Err Reading Messnger
Status during Switch for
[Breaker(s)]

An error was detected in confirming the status of a
Messenger after its firmware has been updated.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution: Settings Update
Failed.Retry will Occur in 30
minutes

An attempt to update the local settings file was
unsuccessful and a retry will be attempted in the
specified time period.

If this error is repeated, Contact GE Post Sales
Service (see

How to contact us on page 2

).

Caution: IP Error X For IP
Address [n.n.n.n]

The HMI encountered an error in establishing a
TFTP session with a CPU.

Note: FTP Error X

An error has occurred during FTP protocol transfer
with a CPU. Contact GE Service.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Note: TFTP Error X

An error has occurred during TFTP protocol transfer
with a CPU. Contact GE Service.

Contact GE Post Sales Service (see

How to

contact us on page 2

).

HMI File [Name] Published OK

The HMI successfully updated the specified file in
the CPU

HMI File [Name] Retrieved OK

The HMI successfully retrieved the specified file
from the CPU

Caution: Error Publishing File
[Name]. Retry

An error has occurred attempting to update the
specified file and a retry will be attempted

Caution: Error Retrieving File
[Name]. Retry

An error has occurred attempting to retrieve the
specified file and a retry will be attempted

Upgrades Downloaded to CPU
OK

The HMI successfully updated the available option
programming for the CPU.

Caution: Upgrades Download
Failed.Unable to Download to
CPU

The HMI was unable to update the available option
programming for the CPU.

Contact GE Post Sales Service if repeated
attempts fail (see

How to contact us

on page 2

).

Setting File Updated for
CPU[A/B]

The settings file has been successfully updated for
the specified CPU.

Can't Update Setting File for
CPU[A/B]

The settings file for the specified CPU could not be
updated.

IP Address in CPUA Written As
[n.n.n.n] From [n.n.n.n]

The IP address in CPU A has been changed as
specified.

Table A-4 HMI/CPU Communications Related Events

Event

Description

Notes and Troubleshooting tips

Advertising