Reduced Energy Let-Thru Mode

142

8

Figure 8-2 Reduced Energy Let-Thru Mode

User Permissions

Only users with "Reduced Let-Thru Mode" permission enabled shall be able to operate RELT. (See
section 4.1 in DEH-500 System Administrator’s Manual)

Default user groups and their RELT permissions:

Factory: Reserved for factory trained service engineers. Can set and remove keys as well

as remove keys set by others.

• Administrator: Can set and remove RELT keys as well as remove keys set by others.
• Operator with RELT: Can set and remove RELT keys.
Operator: Denied the ability set or remove RELT keys.
• Guest: Denied the ability set or remove RELT keys.

Additional groups can be defined with unique permissions.

8.1.2 Enabling Reduced Energy Let-Thru Mode

To enable RELT, On the Master HMI (See section 4.2.2 in DEH-500 System Administrator’s
Manual):

1. Click on the Reduced Energy Let-Thru button on the menu bar

The HMI will enter a “RELT Interactive” mode and the one-line screen with a yellow border
will be displayed. From here, there are three different modes of operation.

2. Choose the type of RELT to initiate: