Alarms and events

284

A

A.2.9 Messenger/Breaker Config Status Events

Alarm Pickup Under-Demand
Flex XX

Under-Demand Flex Relay has entered pickup

Alarm Dropout Under-Demand
Flex XX

Under-Demand Flex Relay has dropped out of
pickup

Alarm Under-Demand Flex XX

Under Demand Alarm Relay has operated

Table A-9 Protection Relay Events

Event

Description

Notes and Troubleshooting tips

Table A-10 Messenger/Breaker Config Status Events

Event

Description

Notes and Troubleshooting tips

Caution Flux Shifter Failure
Reported

Messenger’s Flux Shifter Circuit monitor has
malfunctioned.

Messenger should be replaced
immediately.

Caution Messngr Control Power
1 Lost

Messenger reports that it has lost control power
source 1

Check LINE LED on UPS. If it is off, check
the main power switch on the UPS. If it is
off, turn it on. Otherwise, check the
control power fuse between the
transformer and the UPS.

If the LINE LED is on, check the ON LINE
LED. If it is off, see the UPS manual.

Check UPS fuse.

Contact GE Post Sales Service (see

How

to contact us on page 2

).

Caution Messngr Control Power
2 Lost

Messenger reports that it has lost control power
source 2

Same as control power 1 lost

Messngr Control Power 1 OK

Messenger reports that control power source 1 is
present

Messngr Control Power 2 OK

Messenger reports that control power source 2 is
present

Note Invalid Breaker Type

Messenger reports a breaker type other than ANSI

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid
Frame Rating

Messenger reports a frame rating value that is not
valid, protection settings set to values that are safe
for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Invalid CT
Rating

Messenger reports a CT rating value that is not
valid, protection settings set to values that are safe
for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Protection Defaulted Frame And
CT Mismatch

Messenger reports frame and CT ratings that are
inconsistent, protection settings set to values that
are safe for all frame sizes

Compartment ID button has been
misconfigured, contact GE Post Sales Service
(see

How to contact us on page 2

).

Advertising