Alarms and events description and system troubleshooting guide

283

A

RELT Mode Multipoint - ON / OFF
request from User

Logged when a user enables or disables Multi-point
RELT from the HMI

See section

8

Reduced Energy Let-Thru

Mode on page 139

RELT Mode - ON / OFF request
from User

Logged when a user enables or disables
Single-point RELT from the HMI

See section

8

Reduced Energy Let-Thru

Mode on page 139

RELT Mode System Wide - ON /
OFF request from User

Logged when a user enables or disables System
Wide RELT from the HMI

RELT Mode System Wide - ON /
OFF request from FlexLogic

Logged when FlexLogic enables or disables System
Wide RELT

RELT Mode Multipoint - OFF
request from Modbus Dvc

Logged when a Modbus device initiates Multi-point
RELT mode

RELT Mode System Wide - ON
request from Modbus Dvc

Logged when a Modbus device initiates System
Wide RELT mode

Attention: RELT lock limit
reached - Modbus Device

Logged if more than 8 Modbus devices attempt to
enable RELT for an individual breaker

Attention: RELT Multipt lock limit
reached-Modbus

Logged if more than 8 Modbus devices attempt to
enable Multi-point RELT

Attention: RELT Sys Wide lock
limit reached-Modbus

Logged if more than 8 Modbus devices attempt to
enable System Wide RELT

Attention: RELT failed to initiate -
iButn cfg err

RELT failed due to an IButton error

Attention: RELT failed to initiate -
Comm Loss

RELT failed due to a comm loss

Attention: RELT failed to initiate -
LT Pickup

RELT failed because one of the breakers was in
Long Time Pickup

Attn: RELT MPt failed to
initiate-missing options

Multi-point RELT failed because none of the
Multi-point relays are optioned

RELT Mode Multipoint - ON / OFF
Request From FlexLogic

Logged when FlexLogic enables / disables
multipoint RELT

RELT Mode - ON / OFF Request
From FlexLogic

Logged when FlexLogic enables / disables RELT on
an individual breaker

Over and Under Demand Alarm

Alarm Pickup Over-Demand Flex
XX

Over-Demand Flex Relay has entered pickup

Alarm Dropout Over-Demand
Flex XX

Over-Demand Flex Relay has dropped out of pickup

Alarm Over-Demand Flex XX

Over-Demand Alarm Relay has operated

Table A-9 Protection Relay Events

Event

Description

Notes and Troubleshooting tips