Alarms and events description and system troubleshooting guide

267

A

Attention Messngr
Decommssned Msg Proto Ver

Message protocol version sent by Messenger does
not match what is expected, Messenger
decommissioned

Messenger and CPU are incompatible,
contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr
Decommssned Dupe IDs Seqs

Two Messengers with the same ID have been
detected

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr
Decommssned Dupe Ids

Two Messengers with the same ID have been
detected

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Adv Protection Default To Bus
Cfg 1 Brkr Err

Topology breaker is in an undefined state (i.e. not
open and not closed), therefore system topology
cannot be determined and CPU has defaulted to
bus configuration 1

Breaker service issue, contact GE Post Sales
Service (see

How to contact us on page 2

).

Breaker Topology State Change Breaker topology has changed

Multipoint Relays Topology
State Change

Logged when system topology changes

Adv Protection Default To Bus
Cfg 1 File Err

Configuration files that define the system topology
states is bad or missing, and the CPU has defaulted
to bus configuration 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Invalid Cfg
Card 1

CPU is unable to configure I/O for Card 1

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Invalid Cfg
Card 2

CPU is unable to configure I/O for Card 2

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Discrete IO Disabled Card In
Wrong Slot

Only one I/O card detected, and it is plugged into
PMC1 instead of PMC0

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Caution System Topology
Defaulted

The system has reverted to the default topology
(topology 1). This occurs when the CPU is unable to
determine the state of one or more of the topology
breakers.

Breaker service issue, contact GE Post Sales
Service (see

How to contact us on page 2

).

Attentn PT Sources Defaulted
Invalid Cfg File

The file that describes the PT sources for each
breaker for each topology is invalid. Each breaker is
now using its own voltage information, if any (this is
the default state).

Contact GE Post Sales Service (see

How to

contact us on page 2

).

PT Throwover Has Occurred

Something has caused the system topology to
change (typically a topology breaker has opened or
closed), and the PT sources for some breakers may
have changed.

Messngr Decommissioned
Manual Command

Messenger was decommissioned by a command
received over Modbus

Messngr Commissioned Manual
Command

Messenger was commissioned

ZSI Zone 1…4 Operation

ZSI has udpated the delay times for functions in
zone 1…4

Table A-6 CPU Status Events

Event

Description

Notes and Troubleshooting tips