Overcurrent protection

61

5

5.1.2.2 Accuracy

Pickup accuracy is

±

10% over the entire protection range

5.1.2.3 Setup

The setup required for ST protection is done in the HMI and at the Messenger. There are three
options configured at each Messenger that control the operation of Short Time and
Instantaneous overcurrent protection:

Short Time option

Instantaneous option

Switchable Short Time/Instantaneous option

If the Short Time option or the Instantaneous option (or both) is enabled, the state of the
Switchable ST/IOC option is ignored. The Messenger and Entellisys CPU perform the protection
functions specified by the Short Time and Instantaneous options.

If the Short Time and Instantaneous options are disabled and the Switchable ST/IOC option is
enabled, the Messenger defaults to performing Short Time and digital Instantaneous functions
until instructed otherwise by the Entellisys CPU. In this case, the Messenger does not perform
the analog Instantaneous function. The Entellisys CPU instructs the Messenger to turn on or off
Short Time.

Entellisys limits the maximum Instantaneous Overcurrent Pickup Setting (P

IOC

) Multiplier based

on frame type and whether or not Short Time protection is enabled. This relationship is shown
for EntelliGuard circuit breakers in Table 5-2 below:

Parameters such as IOC pickup, ST pickup, curve type and delay bands for Short Time protection
are set in the HMI, as shown in Figure 5-2.

Table 5-2 Maximum P

IOC

Breaker Frame
Size

Maximum P

IOC

with

Short Time

Maximum P

IOC

without

Short Time

800

15

10

1600

15

10

2000

15

10

3200

13

10

4000

9

9

5000

7

7