GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 199

Advertising
background image

Introduction to FlexLogic

189

11

ELEMENT:
High Resistance
Ground Fault Location

HRGF LOCATION FUNCTION 1 OFF
HRGF LOCATION FUNCTION 1 ON

HRGF Location Function 1 On pulses for the
contactor output - positive logic
HRGF Location Function 1 Off pulses for the
contactor output - negative logic

HRGF LOCATION 2…4

Same set of operands as shown for HRGF
Location 1

ELEMENT:
Instantaneous
Overcurrent

IOC 1 OP
IOC 1 DPO

Instantaneous Overcurrent 1 activated
Instantaneous Overcurrent 1 deactivated

IOC 2…30

Same set of operands as shown for IOC 1

ELEMENT:
Long Time
Overcurrent

LONG TIME 1 PKP
LONG TIME 1 OP
LONG TIME 1 DPO

Long Time Overcurrent 1 in pickup
Long Time Overcurrent 1 tripped breaker
Long Time Overcurrent 1 not in pickup

LONG TIME 2…30

Same set of operands as shown for LONG
TIME 1

ELEMENT:
Multi-Source Ground
Fault

MSGF ZONE 1 TRIP DPO

MSGF ZONE 1 ALARM DPO

MSGF ZONE 1 TRIP PKP

MSGF ZONE 1 ALARM PKP

MSGF ZONE 1 TRIP OP

MSGF ZONE 1 ALARM OP
MSGF ZONE 1 TRIP BACKUP OP

Multi-Source GF Zone 1 trip function not in
pickup
Multi-Source GF Zone 1 alarm function not
in pickup
Multi-Source GF Zone 1 trip function in
pickup
Multi-Source GF Zone 1alarm function in
pickup
Multi-Source GF Zone 1 trip function has
tripped breakers
Multi-Source GF Zone 1 alarm activated
Multi-Source GF Zone 1 trip backup function
has tripped backup breakers

MSGF ZONE 2…4

Same set of operands as shown for MSGF
ZONE 1

Table 11-2 Entellisys FlexLogic operands

OPERAND TYPE

OPERAND SYNTAX

OPERAND DESCRIPTION