Alarms and events

288

A

Caution CPUB Not Rcv From 1
Or More Messngrs

Messenger reports that CPU B is not receiving data
from at least one Messenger (event recorded by
CPU A)

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that Messenger is powered on and
operating.

Caution Messngr Not Receiving
From CPUA

Messenger reports that it is not receiving data from
CPU A

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU A.
Verify that CPU A is powered on and
operating.

Caution Messngr Not Receiving
From CPUB

Messenger reports that it is not receiving data from
CPU B

Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that CPU B is powered on and
operating.

System OK Receiving Broadcast
From CPUA

Messenger reports that it is receiving data from
CPU A

System OK Receiving Broadcast
From CPUB

Messenger reports that it is receiving data from
CPU B

Test Mode Initiated From Test
Kit

Messenger reports that test mode has been
initiated with the test kit

Test Mode Ended From Test Kit

Messenger reports that test mode has ended

Protection Suspended GF From
Test Kit

Messenger reports that ground fault functionality is
to be suspended

Protection Resumed GF From
Test Kit

Messenger reports that ground fault functionality
can resume

Attention Compartment ID
Button Missing

Messenger reports that it has detected that the
compartment ID button is missing

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Note Messngr Error 5

Compartment ID Button contains valid
configuration data, but EEPROM copy is bad

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Caution Check Compartment ID
Button Connection

Messenger reports that the compartment ID button
connection needs to be checked

See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.

Attention Messngr Error 1
Replace ASAP

Messengr reports that its application flash memory
has a CRC error and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Error 2
Replace ASAP

Messengr reports that its boot flash memory has a
CRC error and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Attention Messngr Error 3
Replace ASAP

Messenger reports that it has an analog IOC error
and should be replaced

Contact GE Post Sales Service (see

How to

contact us on page 2

).

Table A-10 Messenger/Breaker Config Status Events

Event

Description

Notes and Troubleshooting tips