Alarms and events
288
A
Caution CPUB Not Rcv From 1
Or More Messngrs
Messenger reports that CPU B is not receiving data
from at least one Messenger (event recorded by
CPU A)
Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that Messenger is powered on and
operating.
Caution Messngr Not Receiving
From CPUA
Messenger reports that it is not receiving data from
CPU A
Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU A.
Verify that CPU A is powered on and
operating.
Caution Messngr Not Receiving
From CPUB
Messenger reports that it is not receiving data from
CPU B
Check Ethernet connection between
Entellisys Messenger and switch, and the
connection between the switch and CPU B.
Verify that CPU B is powered on and
operating.
System OK Receiving Broadcast
From CPUA
Messenger reports that it is receiving data from
CPU A
System OK Receiving Broadcast
From CPUB
Messenger reports that it is receiving data from
CPU B
Test Mode Initiated From Test
Kit
Messenger reports that test mode has been
initiated with the test kit
Test Mode Ended From Test Kit
Messenger reports that test mode has ended
Protection Suspended GF From
Test Kit
Messenger reports that ground fault functionality is
to be suspended
Protection Resumed GF From
Test Kit
Messenger reports that ground fault functionality
can resume
Attention Compartment ID
Button Missing
Messenger reports that it has detected that the
compartment ID button is missing
See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.
Note Messngr Error 5
Compartment ID Button contains valid
configuration data, but EEPROM copy is bad
See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.
Caution Check Compartment ID
Button Connection
Messenger reports that the compartment ID button
connection needs to be checked
See DEH-235 Entellisys Low Voltage
Switchgear EntelliGuard Messenger iButton
Replacement Guide.
Attention Messngr Error 1
Replace ASAP
Messengr reports that its application flash memory
has a CRC error and should be replaced
Contact GE Post Sales Service (see
Attention Messngr Error 2
Replace ASAP
Messengr reports that its boot flash memory has a
CRC error and should be replaced
Contact GE Post Sales Service (see
Attention Messngr Error 3
Replace ASAP
Messenger reports that it has an analog IOC error
and should be replaced
Contact GE Post Sales Service (see
Table A-10 Messenger/Breaker Config Status Events
Event
Description
Notes and Troubleshooting tips