8.2.1 Single-point Overcurrent Settings

Breakers must have ST, IOC or Switchable ST/IOC for single-point RELT to function. RELT
(Topology 0) settings should be reviewed to provide an acceptable level of increased protection
while the system is in Reduced Energy Let - thru mode. See

Section 5: Single-point functions

on page 57

for more information.:

The minimum settings for overcurrent relays for Topology 0 are:

Setting

Value

IOC Enabled

Enabled

IOC Pickup Setting Multiplier

1.5

ST Protection Switch

Enabled

ST Pickup Setting

1.5

ST I2T Curve

Enabled

ST Delay Band Setting

0

LT Delay Band Setting

0

GF Protection Switch

Enabled

GF Trip Priority

0

GF Alarm Enable

Enabled

GF Trip/Alarm Pickup Setting

0.2

GF Trip/Alarm I2T Curve

Enabled

GF Trip/Alarm Delay Band Setting

0