GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 178

Advertising
background image

Discrete I/O

174

10

Input relay blocks

GND
• Connects directly to common on power terminal strip
• No daisy-chaining GND to other relay blocks or “OR” boards
• Inputs from the PMC464 must have a common connection from the PMC464 (pin 17)

running inside cable bundle
• This common connection from the PMC464 must connect to the relay board’s GND

+5V
• One connection directly to +5V power terminal strip
• All additional 5V connections on a single relay input block are daisy-chained within its

own individual input relay block

Output relay blocks

GND
• Redundant output

• GND connected to GND point on the “OR” board
• All additional GND connections on a single relay output block are daisy-chained

within its own individual output relay block

• No daisy-chaining GND to other relay blocks or “OR” boards

• Non-redundant output

• GND connected to common on power terminal strip
• No daisy-chaining GND to other relay blocks
• Outputs from the PMC464 must have a common connection from the PMC464 (pin 17)

running inside cable bundle
• Common connection from PMC464 card should connect to its corresponding

output relay block

• Connect PMC464 common to output relay block GND

+5V
• N/A

“OR” board

+5V
• Connect directly to +5V on power terminal strip

GND
• Connect directly to common on power terminal strip
• No daisy-chaining GND to other “OR” boards or relay blocks
• Output from PMC464 must have a common connection (pin 17) running inside the cable

bundle

• Common connection from PMC464 connects to its corresponding “OR” Board

Twist 5V and GND cables together before connecting to power terminal strip

Power supply

+5V
• Connect directly to +5V on power terminal strip

GND
• Connect directly to GND on power terminal strip

Advertising