Advanced Protection Relays

99

5

5.3.3.2 Trip settings

Relay Enabled: Select Enabled to enable the relay.

Curve Type: Select either Constant time curve or Inverse time curve from the Curve Type
drop-down menu.

Pickup: Adjust the undervoltage pickup from 10% to 95% in increments of 1% from the Pickup
Setting
drop-down menu.

Delay: Adjust the undervoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

Operate if any one phase is below the pickup threshold

Operate if any two phases are below the pickup threshold

Operate if all three phases are below the pickup threshold

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage.

Blocking Voltage Setting: Adjust the blocking voltage from 5% to 75% in increments of 1%
using the Setting drop-down menu in the Blocking Voltage section.

Open Trip: Select the command issued when the relay operates from the Open Trip drop-down
menu. Options are Open and don't activate lockout and Trip and activate lockout.

5.3.3.3 Alarm settings

Relay Enabled: Select Enabled to enable the alarm relay.

Curve Type: Select either Constant time curve or Inverse time curve from the Curve Type
drop-down menu.

Pickup: Adjust the undervoltage pickup from 10% to 95% in increments of 1% from the Pickup
Setting
drop-down menu.

Delay: Adjust the undervoltage delay from 0.5 to 600 seconds in increments of 0.5 seconds from
the Time Delay drop-down menu.

Phase Requirement: Select from among the following options using the Phase Requirement
drop-down menu:

Operate if any one phase is below the pickup threshold

Operate if any two phases are below the pickup threshold

Operate if all three phases are below the pickup threshold

Blocking Voltage Enabled: Select Enabled in the Blocking Voltage section to enable the
blocking voltage.

Blocking Voltage Setting: Adjust the blocking voltage from 5% to 75% in increments of 1%
using the Setting drop-down menu in the Blocking Voltage section.