Reduced Energy Let-Thru Mode

Reduced energy let-thru (RELT) is an optional feature which provides the ability for a user to
quickly adjust the system to temporary settings (usually more sensitive) while in close proximity
to the Entellisys switchgear or downstream equipment.

Topology 0 stores RELT settings for each relay (see below). Topology 0 settings will take
precedence over any topologies until the system is returned to normal.

Highlights

Reduces potential arc flash energy - Increases the sensitivity of the breaker, potentially

lowering the HRC category.

Dynamic ZSI Automatic Adjustment - Breakers in RELT mode will use their RELT settings.

ZSI delays will dynamically adjust all upstream breakers.

Security - Individual user software “keys” are used to track RELT commands per user.
Easy to use - Quickly enable, disable and view RELT with clear graphics on an intuitive

HMI touchscreen interface.

Programmable - RELT can be turned on and off via Modbus TCP, FlexLogic or from an

external device through Discrete I/O.

Flexibility - RELT for a single breaker, group of breakers or the entire lineup can be

executed by a single user input.

Alarming - A Reduced Energy Let-Thru Mode alarm is available for visual and email

notification.

Relays with RELT Settings

Single-point Relays

• Overcurrent relays - IOC, ST, LT and GF

Multi-point Relays

• Bus Differential (BD)
• Multi-Source Ground Fault (MSGF)
• Dynamic Zone Selective Interlock (ZSI)
• High Resistance Ground Fault (HRGF) Priority Tripping

Reduced Energy Let - Thru Modes

Single Breaker RELT - Switches overcurrent relay settings to RELT (Topology 0) for a single

breaker as well as any associated breakers as a group. (See

RELT Groups on page 144

)

Multi-point RELT - This will add a “Multi-point” key and switch all multi-point relays to

RELT (Topology 0) settings as a group.

System Wide RELT - This will add a “System Wide” key and switch settings for all current

relays on all breakers as well as all multi-point relays to RELT (Topology 0) settings.