GE Industrial Solutions Entellisys 5.0 User Manual User Manual

Page 67

Advertising
background image

Overcurrent protection

67

5

There are two options configured at each Messenger for Ground Fault. The combinations of
Ground Fault options are listed in Table 5-5 below.

The parameters for the GF protection provided by the Entellisys CPU can be set in the HMI as
shown in Figure 5-4.

Table 5-5 Ground Fault options

GF Option at
Messenger

Switchable GF
Option at
Messenger

GF Tripping
Priority
Optioned
(HRG
Systems)

GF Trip function
available?

Notes

Enabled

N/A

No

Both CPU and

Messenger

Messenger and CPU perform GF

CPU at user setting, Messenger at
max

GF Alarm is available

UL Listed as a GF Device

Disabled

Enabled

No

Both CPU and

Messenger

GF Trip must be enabled for GF trip to
operate

If disabled, GF Trip will not operate at
either the CPU or Messenger

If enabled, CPU will tell the
Messenger to begin performing GF
(at max setting) while the CPU
performs GF Trip at user settings.

GF Alarm is available

N/A

N/A

Yes

CPU only

GF protection is always disabled at
messenger for HRG system

CPU does NOT set GF at the
messenger when GF Tripping Priority
function is optioned in the system

Disabled

Disabled

No

No

No GF at Messenger or CPU