GE Industrial Solutions Entellisys 5.0 User Manual User Manual
Page 67
Overcurrent protection
67
5
There are two options configured at each Messenger for Ground Fault. The combinations of
Ground Fault options are listed in Table 5-5 below.
The parameters for the GF protection provided by the Entellisys CPU can be set in the HMI as
shown in Figure 5-4.
Table 5-5 Ground Fault options
GF Option at
Messenger
Switchable GF
Option at
Messenger
GF Tripping
Priority
Optioned
(HRG
Systems)
GF Trip function
available?
Notes
Enabled
N/A
No
Both CPU and
Messenger
•
Messenger and CPU perform GF
•
CPU at user setting, Messenger at
max
•
GF Alarm is available
•
UL Listed as a GF Device
Disabled
Enabled
No
Both CPU and
Messenger
•
GF Trip must be enabled for GF trip to
operate
•
If disabled, GF Trip will not operate at
either the CPU or Messenger
•
If enabled, CPU will tell the
Messenger to begin performing GF
(at max setting) while the CPU
performs GF Trip at user settings.
•
GF Alarm is available
N/A
N/A
Yes
CPU only
•
GF protection is always disabled at
messenger for HRG system
•
CPU does NOT set GF at the
messenger when GF Tripping Priority
function is optioned in the system
Disabled
Disabled
No
No
No GF at Messenger or CPU