1

1.3.5 EntelliGuard Messenger

The EntelliGuard Messenger electronic device provides the interface between the circuit
breakers and the CPUs in the Entellisys system.
The following is a summary of the Messenger’s functionality:

Digitizes all switchgear signals

Communicates the raw samples to CPUs via the Messenger network

Controls the circuit breaker

Performs independent backup trip capability at all times

Powered by dual 120v control power sources or self-powered from the current sensors

Provides LED illumination of circuit breaker status, power status, communication status, and
GE “Locator” information

Provides seal-able switches to set CT rating, and (long time) multiplier setting

Provides a test connector for trip curve testing using the Entellisys System Test Kit

1.3.5.1 Messenger User Interface

The Messenger User Interface, as show in Figure 1-7, is described below.

Figure 1-7 Messenger front

LED Indicator Lights

Locate: LED blinks for 10 or 30 seconds on command from the HMI to help operator
physically locate a circuit breaker in the switchgear lineup.

Com1, Com2: Illuminates when Ethernet communication is plugged in and ready to
communicate.

Power: Illuminates when either Control Power A or Control Power B sources are powering the
messenger.

Circuit Breaker Status Open: Illuminates when the circuit breaker is Open. This sensor is
independent of the circuit breaker Close sensor.

Circuit Breaker Status Closed: Illuminates when the circuit breaker is Closed. This sensor is
independent of the circuit breaker Open sensor.

Switches

Rating: Ampere rating of the circuit in use. Maximum value is the CT Rating.

Setting: Multiplier setting for Long Time Overcurrent Protection, specified as X times the
Rating switch value.

Rating Label

Frame: Circuit breaker frame size, in Amperes, represents the maximum continuous-current
rating.

CT: Maximum Ampere rating of the CTs.

Advertising