Reduced Energy Let-Thru Mode

154

8

Click on the RELT Instance and validate that FlexLogic is listed as an Initiating User. (See
figure 8-11)

Figure 8-11 Initiating User - FlexLogic

3. Return to normal by reversing step 1.
4. Test again using the physical input.

8.5 Troubleshooting

Condition: “The Reduced Let-Thru” button is grayed out

RELT is not optioned. See Section 11.2 in DEH 500 System Administrators Manual.

HMI, on initial startup, was not communicating to either CPU.

Condition: Multi-point RELT is grayed out

Verify that at least one of the Multi-point relays are optioned. (BD, MSGF and ZSI)

Condition: Multi-point RELT is enabled but Multi-point RELT status is off

Verify that all of the Multi-point relays are not suspended.

Verify that all zone member circuit breakers are commissioned.

Verify that all zone member circuit breakers are communicating with the CPU.

Verify that the CT ratings are valid for breaker frame.

Configured zones are disabled.

Condition: A breaker has a blinking red highlight after RELT was enabled.

Verify that the breaker is communicating to the CPU.

Verify that the HMI is communicating with the CPUs.

Condition: After turning off RELT, the RELT status remains on.

On each RELT element, verify that neither Modbus Devices nor FlexLogic are still enabled.

On individual breakers, verify that RELT groups are not enabled.