4 mains phase failure monitoring, Mains phase failure monitoring, 5motor control (mctrl) – Lenze 8400 BaseLine C User Manual
Page 107
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
107
5
Motor control (MCTRL)
5.8
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.4
Mains phase failure monitoring
The drive controller has a simple mains-phase failure detection function with which a mains phase
failure can be detected under load.
• In the case of power-adapted machines, approx. 50 % of the rated motor power must be excee-
ded so that a main-phase failure can be detected.
• If the mains phase failure monitoring is tripped:
• The error response set in
will be carried out (Lenze setting: "Warning").
• The "
Su02: Mains voltage switched-off
" error message is entered into the logbook.
Stop!
Under load, the mains input of a three-phase controller can be destroyed if the device is
only supplied by two phases (e.g. if a mains phase fails).