10 parameter reference – Lenze 8400 BaseLine C User Manual

Page 236

Advertising
background image

10

Parameter reference

10.2

Parameter list

236

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00002/13

0: Off / ready

Reserved

C00002/14

0: Off / ready

Reserved

C00002/15

0: Off / ready

Reserved

C00002/16

1: On / start

Enable controller

"1" ≡ Enable controller

"0" ≡ Inhibit controller

C00002/17

0: Off / ready

Activate quick stop

"1" ≡ Activate quick stop

"0" ≡ Deactivate quick stop

C00002/18

0: Off / ready

Reserved

C00002/19

0: Off / ready

Reset error

• After resetting the current error, further errors may be

pending which must be reset as well.

• Details of the currently pending error are displayed in

C00166

.

C00002/20

0: Off / ready

Reserved

C00002/21

0: Off / ready

Delete logbook

• All entries in the controller logbook will be deleted.

• In the logbook, information on the error history is sa-

ved.

C00002/22

0: Off / ready

Reserved

C00002/23

0: Off / ready

Identify motor parameters

• This device command serves to carry out an auto-

matic identification of the motor parameters.

• The device command is only executed when the con-

troller is in the "SwitchedOn" state.

• In order to identify the motor parameters, the cont-

roller must be enabled after this device command.

Identifying motor parameters automatically

C00002/24

0: Off / ready

Reserved

C00002/25

0: Off / ready

Reserved

C00002/26

0: Off / ready

CAN reset node

• Reinitialise "CAN on board" interface.

• Required when changing the baud rate, node address,

or identifiers.

System bus "CAN on board"

C00002/27

0: Off / ready

Reserved

C00002/28

0: Off / ready

Reserved

C00002/29

0: Off / ready

Reserved

C00002/30

0: Off / ready

Reserved

C00002/31

0: Off / ready

Reserved

C00002/32

0: Off / ready

Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00002 | Device commands

Data type: UNSIGNED_8

Index: 24573

d

= 5FFD

h

Advertising