C00010 | minimum analog setpoint, C00011 | appl.: reference speed, C00012 | acceleration time main setpoint – Lenze 8400 BaseLine C User Manual

Page 239: C00013 | deceleration time main setpoint, C012, C011, C013, Leration time, Time, Decel

Advertising
background image

10

Parameter reference

10.2

Parameter list | C00010

239

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00010

C00011

C00012

C00013

Parameter | Name:

C00010 | Minimum analog setpoint

Data type: INTEGER_16

Index: 24565

d

= 5FF5

h

As of version 03.00.00

Lower limit for analog input

Analog terminals

Setting range

(min. value | unit | max. value)

0.0

%

100.0

Subcodes

Lenze setting

Info

C00010/1

0.0 %

Min. analog setpoint

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00011 | Appl.: Reference speed

Data type: UNSIGNED_16

Index: 24564

d

= 5FF4

h

Setting the reference speed

• In the controller, all speed-related signals are processed to one reference variable in percent.

• Set a reference speed here that corresponds to 100 %.

• The frequency of the set reference speed is displayed in

C00059

.

Note:

This is not a maximum limitation!

All values in percent in the controller may be in the range of 0 ... 199.99 %.
Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

9999 1500 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00012 | Acceleration time main setpoint

Data type: UNSIGNED_32

Index: 24563

d

= 5FF3

h

FB

L_NSet_1

: Acceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00013 | Deceleration time main setpoint

Data type: UNSIGNED_32

Index: 24562

d

= 5FF2

h

FB

L_NSet_1

: Deceleration time of the ramp generator for the main speed setpoint

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

999.9 2.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000