3

Commissioning

3.4

Commissioning with the »Engineer«

34

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

2. Adapting the parameters of the motor control:

Tip!
Also check the other information on the nameplate against the motor data set in the drive

controller. You can find further information in the chapter entitled "

Motor selection/Motor

data

".

( 65)

Recommendations for the following application cases:

• If the controller and motor differ greatly from each other in terms of performance:Set

the Imax limit (in motor mode) in

C022

to double the rated motor current.

• If a higher starting torque is required:

In idle state of the motor, set the Vmin boost in

C016

in such a way that the rated motor

current flows at a field frequency of f = 3 Hz (display in

C058

).

• If a high torque is to be available at low speed and without a feedback:Select the "sen-

sorless vector control" (SLVC) in

C006

as motor control.

Parameter

Lenze setting

Info

Value Unit

V/f base frequency

(

C015

)

50.0 Hz

Adapting the V/f base frequency ( 83)

Imax in motor mode

(

C022

)

47.00 A

Optimising the Imax controller ( 85)

Vmin boost

(

C016

)

0.0 %

Adapting the Vmin boost ( 84)