Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

224

9

System bus "CAN on board"

9.9

Implemented CANopen objects | I-1800

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1800

Communication parameter for sending process data via TPDO1

[9-23] Data telegram assignment

How to change the identifier:

1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").

Index:

I-1800

Name:

TPDO1 communication parameter

Subindex

Default setting

Display range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

5

- (read access only)

ro

U8

1: COB-ID used by TPDO

0x180 + node ID

0

4294967295 rw

U32

2: Transmission type

254

0

255 rw

U8

3: Inhibit time

0 ms

0

0.1 ms

65535 rw

U16

4: Reserved

-

- (reserved, read or write access leads to error message

0x06090011)

rw

U8

5: Event timer

0 ms

0

ms

65535 rw

U16

Subindex

Meaning

Code

0

"5" is permanently set.

• Max. 5 subindicesare supported.

-

1

TPDO1 identifier

• According to the "Predefined Connection Set", the

basic setting is: Identifier = 0x180 + node ID

C354/2

2

TPDO transmission type according to DS301 V4.02

Transmission type

( 190)

C322/1

3

Minimum time between sending two identical TPDOs

(see DS301 V4.02).

-

5

Cycle time for PDO transmission with transmission type

"254".

C356/5

C369

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

0/1

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".

Bit

Setting

Bit 30

0 RTR to this PDO possible (Lenze).
1 RTR to this PDO not possible (not adjustable)

Bit 31

0 PDO active
1 PDO inactive