11

Function library

11.1

L_MPot_1

306

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

Parameter

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

Parameter

Possible settings

Info

C800

-199.9

%

199.9 Upper limit

• Lenze setting: 100.0 %

C801

-199.9

%

199.9 Lower limit

• Lenze setting: -100.0 %

C802

0.1

s

999.9 Acceleration time

• Lenze setting: 10.0 s

C803

0.1

s

999.9 Deceleration time

• Lenze setting: 10.0 s

C804

Inactive function

• Selection of response when deac-

tivating the motor potentiometer

via the input bInAct.

0 Keep value

(Lenze setting)

No further action; nOut_a retains its

value.

1 Deceleration to 0

The motor potentiometer returns to

0 % within the deceleration time T

if

.

2 Deceleration to lower limit

The motor potentiometer runs

within the deceleration time T

if

to

the lower limit value (

C801

).

3 Without ramp to 0

Important for the emergency stop

function

The motor potentiometer output im-

mediately changes to 0 %

4 Without ramp to lower limit

The motor potentiometer output im-

mediately changes to the lower limit

value (

C801

).

5 Acceleration to upper limit

The motor potentiometer runs with

the acceleration time T

ir

to the upper

limit value (

C800

).

C805

Init function

• Selection of response when swit-

ching on the device.

0 Load last value

(Lenze setting)

The output value being output du-

ring mains power-off is saved non-

volatilely in the internal memory of

the controller. It will be reloaded du-

ring mains power-on.

1 Load lower limit

The lower limit value (

C801

) is loaded

during mains power-on.

2 Load 0

An output value = 0 % is loaded du-

ring mains power-on.