Parameter reference

10.2

Parameter list | C00029

243

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00029

C00033

C00034

Parameter | Name:

C00029 | AINx: Input current

Data type: INTEGER_16

Index: 24546

d

= 5FE2

h

Display of the input current at the analog input

• When the analog input has been configured for current measurement (

C00034/1

= 1 or 2).

• When

C00034/1

is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.

Analog terminals

Display range

(min. value | unit | max. value)

0.0

mA

20.0

Subcodes

Info

C00029/1

AIN1: Input current

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00033 | AINx: Output value

Data type: INTEGER_16

Index: 24542

d

= 5FDE

h

Display of the output value in percent of the analog input amplifier

• 100 % ≡ 16384 ≡ +10 V / +20 mA

Analog terminals

Display range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Info

C00033/1

AIN1: Output value

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00034 | AINx: Configuration

Data type: UNSIGNED_8

Index: 24541

d

= 5FDD

h

Configuration of the analog input for current or voltage measurement

Analog terminals

Selection list

Info

0 0...+10 V

Input signal is voltage signal 0 V ... +10 V

• 0 V ... +10 V ≡ 0 % ... +100 %

1 0...+5V

With external load resistor (250 Ohms):

Input signal is the current signal 0 mA ... 20 mA

• 0 mA ... 20 mA ≡ 0 % ... +100 %

2 1...+5V (4...20mA)

With external load resistor (250 Ohms):

Input signal is the current signal 4 mA ... 20 mA

• 4 mA ... 20 mA ≡ 0 % ... +100 %

• The current loop is monitored for open circuit

(I < 4 mA) by the device.

Subcodes

Lenze setting

Info

C00034/1

0: 0...+10 V

AIN1: Config.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1