C00085 | motor stator leakage inductance, C00087 | rated motor speed, C00088 | rated motor current – Lenze 8400 BaseLine C User Manual

Page 248: C00089 | rated motor frequency, C088, C089, C087, C085, Akage inductance, Has n

Advertising
background image

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

248

10

Parameter reference

10.2

Parameter list | C00085

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00085

C00087

C00088

C00089

Parameter | Name:

C00085 | Motor stator leakage inductance

Data type: UNSIGNED_16

Index: 24490

d

= 5FAA

h

After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automati-

cally. An automatic detection via the motor parameter identification is possible as well.
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

mH

650.00 0.00 mH

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00087 | Rated motor speed

Data type: UNSIGNED_16

Index: 24488

d

= 5FA8

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor speed for the sensorless vector control (

SLVC

).

Setting range

(min. value | unit | max. value)

Lenze setting

50

rpm

9999 1460 rpm

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00088 | Rated motor current

Data type: UNSIGNED_16

Index: 24487

d

= 5FA7

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.
Setting range

(min. value | unit | max. value)

Lenze setting

0.00

A

99.00 21.00 A

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00089 | Rated motor frequency

Data type: UNSIGNED_16

Index: 24486

d

= 5FA6

h

This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor

catalogue, the suitable value can be entered automatically.

Note:

It is mandatory to give the rated motor frequency for the sensorless vector control (

SLVC

).

Setting range

(min. value | unit | max. value)

Lenze setting

10

Hz

1000 50 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising