I-1016

Monitoring time for the nodes to be monitored via heartbeat.

Heartbeat protocol

( 207)

• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater

value than the heartbeat producer time of the node to be monitored.

[9-12] Data telegram assignment

I-1017

Time interval for sending the heartbeat telegram to the consumer(s).

Heartbeat protocol

( 207)

• The parameterised time is rounded down to an integer multiple of 5 ms.
• The heartbeat telegram is automatically sent as soon as a time > 0 ms is entered. In this case,

the "node guarding" monitoring function is deactivated.

• This object relates to code

C381

.

Index:

I-1016

Name:

Consumer heartbeat time

Subindex

Default setting

Display range (min. value | unit | max. value)

Access

Data type

0: Highest subindex supported

BaseLine C: 1

StateLine C: 7

HighLine C: 15

TopLine C: 15

- (read access only)

ro

U16

1 ... n: Consumer heartbeat time

0

0

65535 rw

U16

Subindex

Meaning

Lenze code

0

Number of nodes to be monitored

1 ... n

Node ID and heartbeat time of the node to be monitored Node ID:

C385/x

Heartbeat time:

C386/x

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31 ... bit 24

Bit 23 ... bit 16

Bit 15 ... bit 0

0

(reserved)

Node ID

Heartbeat time

in [ms]

Index:

I-1017

Name:

Producer heartbeat time

Subindex

Default setting

Display range (min. value | unit | max. value)

Access

Data type

0: Producer heartbeat time

0

0

ms

65535 rw

U16