3commissioning – Lenze 8400 BaseLine C User Manual

Page 38

Advertising
background image

3

Commissioning

3.4

Commissioning with the »Engineer«

38

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Diagnostics options
When the »Engineer« is used, trouble during commissioning can be detected and eliminated conve-

niently. Proceed as follows:

• Check whether error messages appear in the »Engineer«.

• You can find a description of each possible message in the chapter entitled "

Diagnostics &

error management

".

( 145)

• Check the input terminals for their corresponding setpoints.

• The Terminal assignment tab displays the current input/output signals.

• Check the signal flow of the application.

• To do this, open the Application Parameters tab and click on the Signal flow button. The sig-

nal flow which is then shown enables a view of the setpoints being applied and their proces-

sing.

Advertising