C00994
Parameter | Name:
C00994 - Flying restart fct.: Current
Data type: INTEGER_16
Index: 23581
d
= 5C1D
h
Current to be injected during the flying restart process
• 100 % ≡ rated motor current (
• The flying restart current should amount to 10 ... 25 % of the rated motor current.
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
100.0 25.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100