C00994 - flying restart fct.: current, C994, 10 parameter reference – Lenze 8400 BaseLine C User Manual

Page 297

Advertising
background image

10

Parameter reference

10.2

Parameter list | C00994

297

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00994

Parameter | Name:

C00994 - Flying restart fct.: Current

Data type: INTEGER_16

Index: 23581

d

= 5C1D

h

Current to be injected during the flying restart process

• 100 % ≡ rated motor current (

C00081

).

• The flying restart current should amount to 10 ... 25 % of the rated motor current.

Flying restart function

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

100.0 25.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100