Device control (DCTRL)

4.2

Device states

54

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

• The change from one state to another is done in a 1 ms cycle. If, at the same time, several state

change requests exist, the state with the higher priority is processed first (see the following ta-

ble).

C137

displays the current device state.

C150

(status word) provides a bit coded representation of the current device state via bits 8 ... 11

(see table below).

[4-1]

Device states, priorities, and meaning of the status bits in the status word

ID Device state

(Display in

C137

)

Priority

Status bits

(display in

C150

)

Meaning

Bit 11 Bit 10 Bit 9

Bit 8

0 - (reserved)

-

0

0

0

0

-

1

Init

-

0

0

0

1

Initialisation is active

2

MotorIdent

-

0

0

1

0

Motor parameter identification is acti-

ve

3

ReadyToSwitchON

Prio 4

0

0

1

1

Device is ready to start

4

SwitchedON

Prio 3

0

1

0

0

Device is switched on

5

OperationEnabled

Prio 1

0

1

0

1

Operation

6 - (reserved)

-

0

1

1

0

-

7

Trouble

Prio 2

0

1

1

1

Trouble is active

8

Fault

Prio 6

1

0

0

0

Fault is active

9 - (reserved)

-

1

0

0

1

-

10

SafeTorqueOff

Prio 5

1

0

1

0

Safe torque off is active

11 - (reserved)

-

1

0

1

1

-

... ...

...

...

...

15 - (reserved)

-

1

1

1

1

-