9system bus "can on board – Lenze 8400 BaseLine C User Manual

Page 191

Advertising
background image

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

191

9

System bus "CAN on board"

9.6

Process data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

The communication parameters such as the transmission mode and cycle time can be set freely for

every PDO and independently of the settings of other PDOs:

Blocking time
In

C00324/x

, an "inhibit time" can be set that defines the shortest transmission cycle for the "asyn-

chronous - manufacturer-specific/device-profile specific" transmission type.
Example: Cycle time = 500 ms, blocking time = 100 ms, sporadic data change:

• In case of a sporadic data change < 500 ms, fastest transmission is every 100 ms (event-cont-

rolled transmission). The transmission cycle timer is reset to 0 if the transmission has been trig-

gered in an event-controlled manner.

• In case of a sporadic data change > 500 ms, fastest transmission is every 500 ms due to the set

blocking time (cyclic transmission).

Tip!
The setting can also be carried out via the following CANopen objects:

I-1400

...

I-1401

: Communication parameters for RPDO1 ... RPDO2

I-1800

...

I-1801

: Communication parameters for TPDO1 ... TPDO2

Parameter

Info

Lenze setting

Value Unit

CAN1_OUT

C00322/1

Transmission mode

254

C00324/2

Blocking time

0 ms

C00356/5

Cycle time

0 ms

CAN2_OUT

C00322/2

Transmission mode

254

C00324/3

Blocking time

0 ms

C00356/2

Cycle time

0 ms

CAN1_IN ... CAN2_IN

C00323/1...2

Transmission mode CAN1_IN ... CAN2_IN

• For RPDO, it serves as monitoring setting

in the case of sync-controlled PDOs.

254