Diagnostics & error management

8.6

Maloperation of the drive

154

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.6

Maloperation of the drive

Maloperation

Cause

Remedy

Motor does not rota-

te

DC-bus voltage is too low

• Red LED is blinking every 1 s

Check mains voltage

Controller is inhibited

• Green LED is blinking

Deactivate controller inhibit

• Note: Controller inhibit can be set via se-

veral sources !

C158

displays all active sources for cont-

roller inhibit.

Automatic start is inhibited

LOW/HIGH edge at RFR

If required, correct auto-start option in

C142

.

"Inhibit at power-on" auto-start option

DC-injection braking (DCB) is active

Deactivate

DC-injection braking

Mechanical motor brake is not released

Release mechanical motor brake manually or

electrically

Quick stop (QSP) active

Deactivate quick stop

• Note: Quick stop can be set via several

sources!

C159

displays all active sources for quick

stop.

Setpoint = 0

Select setpoint

Setpoint = 0 with activated fixed setpoint

Set fixed setpoint in

C039/1...3

Trouble is active

Clear fault

With

C006

= 4 zwar "SLVC: Vector control"

has been set, but no motor parameter identi-

fication has been carried out.

Carry out automatic motor parameter identi-

fication with the

C002/23

device command.

Automatic motor data identification

Assignment of several mutually exclusive

functions with a signal source in

C701

Correct configuration in

C701

.

Motor rotates irregu-

larly

Motor cable is defective

Check motor cable

Maximum motor current in motor or genera-

tor mode is set too low

Adjust settings to the application:

C022

:

Imax in motor mode

C023

: Imax in generator mode

Motor is underexcited or overexcited

Check parameterisation:

C006

: Motor control

C015

: VFC: V/f base frequency

C016

: VFC: Vmin boost

Rated motor data (stator resistance, speed,

current, frequency, voltage) and cos ϕ and/

or magnetising inductance is not adapted to

the motor data

Carry out automatic motor parameter identi-

fication with the

C002/23

device command

- or -

Adjust motor parameters manually:

C084

: Motor stator resistance

C087

: Rated motor speed

C088

: Rated motor current

C089

: Rated motor frequency

C090

: Rated motor voltage

C091

: Motor cosine phi

C092

: Motor magnetising inductance

Motor windings are wired incorrectly

Reverse from star connection to delta con-

nection