C00324 | can transmit blocking time, C00345 | can error status, C345 – Lenze 8400 BaseLine C User Manual

Page 268: C00324/x, C00324/2, C00324/3, 10 parameter reference

Advertising
background image

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

268

10

Parameter reference

10.2

Parameter list | C00324

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00324

C00345

Parameter | Name:

C00324 | CAN transmit blocking time

Data type: UNSIGNED_16

Index: 24251

d

= 5EBB

h

As of version 03.03.00

Blocking time for transmitting the emergency telegram and the process data

Note:

If the "asynchronous - manufacturer-specific/device-profile specific" transmission type has been set, the transmis-

sion cycle timer is reset to 0 if transmission has been triggered in an event-controlled manner.

Example: Cycle time (

C00356/x

) = 500 ms, blocking time = 100 ms, sporadic data change:

• In case of a sporadic data change < 500 ms, fastest transmission is every 100 ms due to the set blocking time

(event-controlled transmission).

• In case of a sporadic data change > 500 ms, fastest transmission is every 500 ms due to the set blocking time (cy-

clic transmission).

System bus "CAN on board"

Setting range

(min. value | unit | max. value)

0

ms

6500

Subcodes

Lenze setting

Info

C00324/1

0 ms

Emergency blocking time

C00324/2

0 ms

CAN1_OUT blocking time

C00324/3

0 ms

CAN2_OUT blocking time

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00345 | CAN error status

Data type: UNSIGNED_8

Index: 24230

d

= 5EA6

h

System bus "CAN on board"

Selection list

(read only)

0 No Error
1 Warning ErrActive
2 Warning ErrPassive
3 Bus off
4 Reserved
5 Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1