C00052 | motor voltage, C00053 | dc-bus voltage, C00054 | motor current – Lenze 8400 BaseLine C User Manual

Page 245: C00056 | torque, C00057 | maximum torque, C052, C053, C054, C057, C056/2

Advertising
background image

10

Parameter reference

10.2

Parameter list | C00052

245

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00052

C00053

C00054

C00056

C00057

Parameter | Name:

C00052 | Motor voltage

Data type: UNSIGNED_16

Index: 24523

d

= 5FCB

h

Display of the current motor voltage/output voltage of the inverter
Display range

(min. value | unit | max. value)

0

V

1000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00053 | DC-bus voltage

Data type: UNSIGNED_16

Index: 24522

d

= 5FCA

h

Display of the current DC-bus voltage
Display range

(min. value | unit | max. value)

0

V

1000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00054 | Motor current

Data type: UNSIGNED_16

Index: 24521

d

= 5FC9

h

Display of the current motor current/output current of the inverter
Display range

(min. value | unit | max. value)

0.00

A

300.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00056 | Torque

Data type: INTEGER_32

Index: 24519

d

= 5FC7

h

Display of the current torque
Display range

(min. value | unit | max. value)

-99.00

Nm

99.00

Subcodes

Info

C00056/1

Torque setpoint

• Only with sensorless vector control (

SLVC

).

C00056/2

Actual torque

• Estimated actual torque for all motor control modes.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00057 | Maximum torque

Data type: UNSIGNED_32

Index: 24518

d

= 5FC6

h

Display of the maximum torque to be generated by the motor

• The maximum torque to be generated by the motor depends on various factors, e.g. on Imax in motor mode

(

C00022

) and the motor type used.

Display range

(min. value | unit | max. value)

0.0

Nm

999.9

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100