10.2

Parameter list | C00024

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00024

C00026

C00027

C00028

Parameter | Name:

C00024 | Comparison value N_Act

Data type: INTEGER_16

Index: 24551

d

= 5FE7

h

Threshold for the actual speed comparison

• This parameter serves to set a threshold that is compared with the actual speed value.

• When the value falls below this threshold, the bNactCompare output of the SB

LS_DriveInterface

switches to

TRUE.

• Switching hysteresis = +1 %

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

199.9 0.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00026 | AINx: Offset

Data type: INTEGER_16

Index: 24549

d

= 5FE5

h

Offset for analog input

Analog terminals

Setting range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Lenze setting

Info

C00026/1

0.0 %

AIN1: Offset

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00027 | AINx: Gain

Data type: INTEGER_32

Index: 24548

d

= 5FE4

h

Gain for analog input

Analog terminals

Setting range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Lenze setting

Info

C00027/1

100.0 %

AIN1: Gain

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00028 | AINx: Input voltage

Data type: INTEGER_16

Index: 24547

d

= 5FE3

h

Display of the input voltage at the analog input

Analog terminals

Display range

(min. value | unit | max. value)

-10.0

V

10.0

Subcodes

Info

C00028/1

AIN1: Input voltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100