Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

193

9

System bus "CAN on board"

9.6

Process data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.5

Monitoring of the RPDOs for data reception

Every RPDO1 ... RPDO2 has a parameterisable monitoring time in which the RPDO must arrive. If the

RPDO is not received within the monitoring time or with the configured sync, the response parame-

terised for the respective RPDO is activated.

Short overview: Parameters for RPDO monitoring

Parameter

Info

Lenze setting

Value Unit

C357/1

CAN1_IN monitoring time

3000 ms

C357/2

CAN2_IN monitoring time

3000 ms

C593/1

Resp. to CAN1_IN monitoring

No response

C593/2

Resp. to CAN2_IN monitoring

No response