C00036 | dcb: current, C00039 | fixed setpoint x (l_nset_1 n-fix), C00050 | mctrl: speed setpoint – Lenze 8400 BaseLine C User Manual

Page 244: C00051 | mctrl: actual speed value, C039, C051, C039/1, C039/2, C039/3, Is used as setpoint speed

Advertising
background image

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

244

10

Parameter reference

10.2

Parameter list | C00036

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00036

C00039

C00050

C00051

Parameter | Name:

C00036 | DCB: Current

Data type: INTEGER_16

Index: 24539

d

= 5FDB

h

Current value in [%] for DC-injection braking

• 100 % ≡ Imax in motor mode (

C00022

)

DC injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%

150.0 50.0 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00039 | Fixed setpoint x (L_NSet_1 n-Fix)

Data type: INTEGER_16

Index: 24536

d

= 5FD8

h

FB

L_NSet_1

: Fixed speed setpoints (JOG values) for the setpoint generator

Setting range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Lenze setting

Info

C00039/1

40.0 %

Fixed setpoint 1

C00039/2

60.0 %

Fixed setpoint 2

C00039/3

80.0 %

Fixed setpoint 3

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00050 | MCTRL: Speed setpoint

Data type: INTEGER_32

Index: 24525

d

= 5FCD

h

Display of the speed setpoint at the speed setpoint input of the motor control
Display range

(min. value | unit | max. value)

-9999

rpm

9999

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00051 | MCTRL: Actual speed value

Data type: INTEGER_32

Index: 24524

d

= 5FCC

h

Display of the actual speed value of the motor shaft

Note:

The displayed value only corresponds to the real actual speed value of the motor shaft if an encoder is connected to

the motor and the evaluation of the feedback signal has been set correctly ("Closed loop" operation).

In case of operation without speed feedback, the signal is calculated from the motor control and thus may not cor-

respond to the real actual speed.
Display range

(min. value | unit | max. value)

-9999

rpm

9999

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1