1 available process data objects, Available process data objects, 9system bus "can on board – Lenze 8400 BaseLine C User Manual

Page 184

Advertising
background image

9

System bus "CAN on board"

9.6

Process data transfer

184

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.1

Available process data objects

8400 BaseLine C controllers have a maximum number of 2 receive PDOs (RPDOs) and 2 transmit

PDOs (TPDOs).

Receive PDOs (RPDOs)
The process data objects transmitted from the CAN bus to the drive are processed via the

LP_CanIn1

and

LP_CanIn2

port blocks.

• Every port block provides 4 words (2 bytes/word). The data of every first word are provided in a

bit decoded manner (bit 0 ... 15).

• The first word of the

LP_CanIn1

port block is defined as control word.

• For the predefined assignment, see the "

Process data assignment for control via CAN

" sub-

chapter for drive application.

Transmit PDOs (TPDOs)
The process data objects transmitted from the drive to the CAN bus are processed via the

LP_CanOut1

and

LP_CanOut2

port blocks.

• Every port block receives 4 words (2 bytes/word). The data of every first word are transmitted

bit by bit (bit 0 ... 15).

• The first word of the

LP_CanOut1

port block is defined as status word.

• For the predefined assignment, see the "

Process data assignment for control via CAN

" sub-

chapter for drive application.

The preconfigured interconnection of the internal interfaces for a control via CAN is

shown in chapter "Drive application" in figure

[7-2]

.

( 136)