background image

3

Commissioning

3.4

Commissioning with the »Engineer«

36

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4. Adapt parameters of the application:

Tip!

• Via the Signal flow button, you get one dialog level lower to the signal flow of the appli-

cation with further parameterisation opportunities. See chapter entitled

"

Parameterisation dialog

".

( 122)

• The preconfigured I/O connection in the selected control mode can be changed via con-

figuration parameters. See chapter entitled "

User-defined terminal assignment

".

( 114)

More detailed information on the drive application:

Drive application

( 121)

Interface description

( 127)

Setting parameters (short overview)

( 132)

Pre-assignment of the drive application

( 133)

Terminal assignment of the control modes

( 139)

Parameter

Lenze setting

Info

Value Unit

Accel. time - main setpoint

(

C012

)

2.0 s

The setpoint is led via a ramp function generator with li-

near characteristic. The ramp function generator con-

verts setpoint step-changes at the input into a ramp.

L_NSet_1 ( 309)

Decel. time - main setpoint

(

C013

)

2.0 s

Reference speed

(

C011

)

1500 rpm

All speed setpoint selections are provided in % and al-

ways refer to the reference speed set in

C011

.

The motor reference speed is given on the motor name-

plate.

Deceleration time - quick

stop

(

C105

)

5.0 s

When "quick stop" is requested, the motor control is de-

coupled from the setpoint selection and within the de-

celeration time parameterised in

C105

, the motor is

brought to a standstill in (n

act

= 0).

Activate/Deactivate quick stop ( 50)

Fixed setpoint 1

(

C039/1

)

40.0 %

A fixed setpoint for the setpoint generator can be acti-

vated instead of the main setpoint via the digital inputs

DI1 and DI2.

• The fixed setpoints are selected in [%] based on the

reference speed (

C011

).

L_NSet_1 ( 309)

Fixed setpoint 2

(

C039/2

)

60.0 %

Fixed setpoint 3

(

C039/3

)

80.0 %