Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

173

9

System bus "CAN on board"

9.1

General information

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.1.4

Activating the bus terminating resistor

The CAN bus has to be terminated at the first and last physical node each by a resistor (120 Ω) bet-

ween CAN low and CAN high:

[9-1]

Terminations at the beginning and end of the CAN bus

9.1.5

Setting baud rate & node address

The baud rate is set via code

C351

.

• Options: 20, 50, 125, 250, 500, 1000 kbps
• Lenze setting: 500 kbps

The node address is set via code

C350

.

• Valid address range: 1 to 63

8400

BaseLine C

CH
CL
CG

120

R

CAN

120

R

L

OW

G

N

D

I/

OS

hiel

d

s

CH

CL

CG

X1

HI

G

H

X13

Note!

The addresses of the nodes must differ from each other.