Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05

59

4

Device control (DCTRL)

4.2

Device states

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.6

OperationEnabled

In the "OperationEnabled" state

• is the controller if the controller inhibit is deactivated and no trouble ("Trouble") and fault

("Fault") are existent.

• the operation is enabled and the motor follows the setpoint defined by the active application

(in case of sensorless vector control only after the magnetisation process is completed).

Depending on certain conditions, a state change takes place based on the "OperationEnabled" de-

vice state.

Related topics:

Process data assignment for control via CAN

( 137)

LED DRIVE READY

LED DRIVE ERROR

Display in

C137

Display in status word 1 (

C150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

OperationEnabled

0

1

0

1

Change condition

Changeover to the device state

Control bit "EnableOperation" in control word wCANControl = "0"

OR terminal RFR = LOW level (controller inhibit).

SwitchedON

Control bit "SwitchOn" = "0".

ReadyToSwitchON

Undervoltage in the DC bus.

Trouble

/

Fault

(dependent on

C600/1

)

Error with error response "Trouble" occurs.